AMC3200 Series

AMC3200 Series

The Aliamag AMC3200 series converter is a microprocessor based intelligent transmitter that can be paired with any of the Alia AMF series sensors. The unit features multiple display parameters including flow rate, flow total, diagnostics, programming and troubleshooting.
It’s equipped with bluetooth, HART and Modbus communication functions.

Download

 

 

 

FEATURES

  • Three line LCD display Flow Rate / Totalizer
  • Accuracy of +/-0.2% value of reading
  • Bi-directional flow measurement, current and pulse output
  • Explosion Proof, Exd(ib)ibqllBT5
  • Bluetooth/MODBUS/HART communication
  • Converter can be rotated at Four directions for easy installation

SPECIFICATION

Excitation: Keypad:
DC pulsed 3 internal keys for programming 
Display: and display control
3 lines LCD with illumination Data Storage:
Line 1 Operation parameters and totalizer
11 digit totalizer for forward flow figures are stored by EEPROM for more
11 digit totalizer for reverse flow than 10 years
11 digit totalizer for difference Low Flow Cutoff:
Line 2 0 to 9.9 %
5 digit flowrate / velocity / % / mA / HZ Damping:
Line 3 0 to 99 Seconds
Parameter / Query / Clr tot / Query LOG Density Setting:
Alarm, Guidance 0.1 to 9.99 g/cm3
Totalizer Unit Self Diagnosis:
T, Kg, g, lb, Ston, Lton,m3,L,mL,Igal, gal, The following error message are
Mgal£¬bbl, ft3, a-ft   displayed if failure occurs
Time Unit – Coil failure
sec, min, hour, day – Power failure
Measuring Range: – Overanged Output
Min.  0 to 0.15 m/s – Internal error
Max. 0 to 15 m/s – Overflow
Accuracy: – Empty pipe
+/-0.2% of reading (Velocity >=0.5 m/s) Cable Entry:
+/-0.001 m/s (Velocity < 0.5 m/s) Standard :M20   Option:1/2″NPTF
Repeatability: Protection Class:
+/-0.05% of reading IP 67, Explosion proof, Exd(ib)ibqllBT5
Current Output: Ambient Temperature:
4-20 mA (Isolated) -25 to +65 oC
Load Material:
Max. 600 Aluminum Alloy
Pulse Output: Power Supply:
Open collector 90-260 Vac, 50/60 Hz
Rating 24Vdc +/-10% (Option)
3 to 30 Vdc, 50 mA Max.  Power Consumption:
Pulse Rate: 3-17 W (Dependent on sensor size)
1)Scale pulse (Pulse/mL, Pulse/L, Other) Weight:
2)Frequency: 0-5000 Hz 4.5 Kg
Pulse Width: Mounting:
50% of band width Bracket on 2″ pipe
Alarm:
High/Low with open collector output
Rating
3 to 30 Vdc, 50 mA Max. 
Communication:
Bluetooth (Android)Standard
RS485 (MODBUS Protocol)Standard
HART signal (Compatible)Optional