AMC2100 Series
AMC2100 Series
The Aliamag AMC2100 series converter is a microprocessor based intelligent transmitter that can be paired with any of the Alia AMF series sensors. The unit features multiple display parameters including flow rate, flow total, diagnostics, programming and troubleshooting.
FEATURES
- Three line LCD display Flow Rate / Totalizer
- Accuracy of +/-0.4% value of reading
- Bi-directional flow measurement, current and pulse output
- Large digital display
- Records up to 99 power on/off time
- MODBUS/HART communication
SPECIFICATION
Excitation: | Keyboard: | |
DC pulsed | 3 external keys for programming | |
Display: | and display control | |
3 lines LCD with illumination | Low Flow Cutoff: | |
Line 1 | 0 to 9.9 % | |
11 digit totalizer for forward flow | Data logger Function: | |
11 digit totalizer for reverse flow | 99 times flowrate records for power on/off | |
11 digit totalizer for difference | Record Data: | |
Line 2 | Date/Time when Power on/off | |
5 digit flowrate / velocity / % / mA / HZ | Flow rate when Power on/off | |
Line 3 | Totalizer when Power on/off | |
Parameter / Query / Clr tot / Query LOG | Damping: | |
Alarm, Guidance | 0 to 99 Seconds | |
Unit | Density Setting: | |
M3/H, L/H, Kg/H, T/H, L/min, M3/min, GPH | 0.1 to 9.99 g/cm3 | |
GPM, ML/H, ML/m, ML/sec | Self Diagnosis: | |
Measuring Range: | The following error message are | |
Min. 0 to 0.15 m/s | displayed if failure occurs | |
Max. 0 to 15 m/s | – Coil failure | |
Accuracy: | – Power failure | |
+/-0.4% read-out values (Velocity >=0.5 m/s) | – Overranged output | |
+/-0.002 m/s (Velocity < 0.5 m/s) | – Internal error | |
Repeatability: | – Overflow | |
+/-0.1% read-out values | – Empty pipe | |
Current Output: | Cable Entry: | |
4-20 mA (Isolated) | Standard :PG11 Option:1/2″NPTF | |
Load | Protection Class: | |
Max. 600 | IP 65 | |
Pulse output: | Ambient Temperature: | |
Open collector |
|
|
Rating | Material: | |
3 to 30 VDC, 20 mA Max. | Aluminum Alloy | |
Pulse Rate: | Power Supply: | |
1)Scale pulse (Pusle/M3, Pulse/L, Other) | 90-260 VAC, 50/60 Hz | |
2)Frequency: 0-5000 Hz | 24VDC +/-10% (Option) | |
Pulse Width: | Power Consumption: | |
50% of band width | 3-17 W (Dependent on sensor size) | |
Alarm: | Weight: | |
High/Low with open collector output | 1.4 Kg | |
Rating | Mounting: | |
3 to 30 VDC, 20 mA Max. | Wall mounting | |
Communication: | Bracket on 2″ pipe | |
RS 485 (MODBUS Protocol) | ||
HART signal (Compatible) | ||
Data Storage: | ||
Operation parameters and totalizer | ||
figures are stored by EEPROM for more | ||
than 10 years |